1660603937568 Air Pressure

Are VSD-controlled compressors best for regulating air pressure?

March 16, 2011
Determine the best configuration to regulate compressed air pressure.
Figure 1. Airflow through an orifice as a function of pressure.

The idea of regulating the compressed air pressure of the whole plant from one location is a fairly new innovation. Operating a compressed air system at the lowest optimum pressure to meet the needs of production reduces energy cost. But there’s a controversy: Should compressed air pressure/flow control be used, or should modern compressor controls, especially VSD-controlled compressors, be used as an alternative to providing precise pressure regulation? Or is the best configuration using both?

What is artificial demand?

Artificial demand is defined as the excess volume of air that is required by unregulated end uses as a result of supplying higher pressure than necessary for applications. Compressed air flows from the compressed air system to atmosphere through an opening or hole in the system. That opening could be a leak, an air tool, a pneumatic cylinder, control valve or other production application. If there’s a hole or orifice in the air system, increasing compressed air pressure increases the airflow (Figure 1).

Flow rates for various orifice sizes and pressures are shown in Table 1. A 10-psig reduction in air pressure causes approximately 10% less compressed airflow.

Orifice (in.)   Pressure (psi)
  90 100 125
1/16 5.92 6.49 7.9
1/8 23.7 26 31.6
1/4 94.8 104 126
3/8 213 234 284
1/2 379 415 506
Table 1. Flow rate (in SCFM) for various orifice sizes (Source: Best Practices for Compressed Air Systems)
To read the rest of the this article, please visit our sister publication Plant Services >> http://www.plantservices.com/articles/2011/03VSDControlledCompressors.html 

Sponsored Recommendations

Many facilities handle dangerous processes and products on a daily basis. Keeping everything under control demands well-trained people working with the best equipment.
Enhance the training experience and increase retention by training hands-on in Emerson's Interactive Plant Environment. Build skills here so you have them where and when it matters...
See how Rosemount™ 625IR Fixed Gas Detector helps keep workers safe with ultra-fast response times to detect hydrocarbon gases before they can create dangerous situations.
The Micro Motion 4700 Coriolis Transmitter offers a compact C1D1 (Zone 1) housing. Bluetooth and Smart Meter Verification are available.