Get Your Head Around Shutoff Head

Specifying control valves that may need to provide tight cutoff requires care

By Dirk Willard, Contributing Editor

A data sheet for a reactor flow-control valve called for a “shutoff head.” Given that this control valve handled ethylene oxide (EO), a highly volatile and reactive compound, the requirement gave me pause. Addressing it involved more than defining the pump deadhead pressure. Here’re some thoughts to consider.

First, it’s important to understand that a control valve isn’t a shutoff valve. A control valve must provide precise adjustments to flow. Crunching down on the plug to block flow can cause damage. The actuator and linkage of a control valve aren’t designed for tight shutoff; a shutoff valve’s actuator is. If you want to prevent leakage, install a shutoff valve.

Unfortunately, no standards define control-valve shutoff head. A few describe leakage through the body of a valve; this leakage is categorized poorly as Class I-VI in ANSI/FCI 70-2, “Control Valve Seat Leakage.” Valves also leak from their stems. For stem leakage, refer to ISO-15848, “Industrial Valves — Measurement, Test and Qualification Procedures for Emissions – Part 1...” This specification is best because it recommends helium as the test medium. API-622, “Type Testing of Process Valve Packing for Fugitive Emissions,” also describes stem leakage but for methane.

However, we’re concerned about defining the shutoff head for a control valve specification, not leakage. For this, understanding the limits of valve body type is important. Obviously, butterfly valves won’t provide tight shutoff — although I have seen them used where leaking is acceptable, such as where thermal expansion is allowed. Be aware that thermal expansion could cause the valve seat to stretch or dislodge. In this case, the valve itself limits the shutoff head. Butterfly valves are available with shutoff heads of 175 psi and up, but, in practical terms, the limit is more like 50 psi or less. Diaphragm and other soft-seat valves have the same problem. Gate valves, with their exposed seats and metal-on-metal sealing surfaces, are a bad choice. Globe valves, while often most effective for control, are the worst option. Ball and plug valves probably offer the best choice for shutoff.

Lack of mechanical strength is a common problem with soft seats but less of an issue with hard, metal-on-metal seats. Soft seats are best for sealing against streams containing solids, such as slurries. Hard surfaces, polished smooth, work best at high temperatures, above 250°F, where polymers begin to break down or flow; solids quickly ruin polished surfaces. Fluoropolymers can extend the range of soft seats to 350°F. However, hard plastics retain memory and can be scratched just like metal; memory retention gets worse above 200°F. Partially-fluorinated polymers generally outperform polytetrafluoroethylene (PTFE) in fabricated liners but PTFE serves well as sheets. Ceramics offer a useful alternative to metal in erosive environments but not without sacrificing tight shutoff.

Enough about the peripherals, let’s get down to specifications. Several scenarios can define shutoff head: 1) flow provided by a mover, e.g., a pump or compressor; 2) pressure isolation; 3) temperature control; and 4) safety, i.e., prevention of a chemical reaction. In the first case, use the deadhead pressure of the mover. (Deadhead is the extreme left corner on a pump curve.) For a pump, pick the deadhead for the largest impeller possible. For temperature control, use the regulator steam pressure — unless a significant risk is present and the steam is stepped down, in which case use the original pressure. Safety is a tricky subject.

If a chemical such as EO is involved, safety trumps a pump curve. EO leaking past the isolation valves to the reactor could lead to a release or worse. In this situation, as in the others requiring a tradeoff between control and isolation, don’t rely on a control valve for shutoff: put automatic valves upstream and downstream of the control valve for isolation. Install pressure switches and pressure transmitters to monitor thermal expansion and use thermal relief valves to blow expanding liquids back to storage. Both switches and transmitters are valuable because transmitters are limited to <100-ms response time and switches don’t trend.

Lastly, let’s look at actuators. If a control valve is to function as a reliable shutoff valve, a positioner is an absolute necessity. Ideally, use one with a 0–100% position indicator. Specify an open-and-closed position indicator for all automatic valves used for shutoff. Take care in selecting the actuator air pressure and supply; evaluate the pressure reliability before selection; plan for 1 scfm of air per control valve or automatic valve that’s 6 in. or less in size.


dirk.jpgDIRK WILLARD is a Chemical Processing contributing editor. He recently won recognition for his Field Notes column from the ASBPE. Chemical Processing is proud to have him on board. You can e-mail him at dwillard@putman.net

More from this perspective...

Title

Avoid Job Hunting Pitfalls

Heed a few tips to forestall frustrations.

07/08/2013

Defuse Dust Dangers

Carefully consider and then counter risks of fire and explosion

08/27/2013

Field Notes: Gun For Better Troubleshooting

Surface temperature measurements often can provide valuable insights.

09/11/2013

Safety: Douse a Burning Issue

You're not as safe as some fire safety tests may lead you to believe.

10/22/2013

Avoid Project Management Mistakes

A number of common mistakes can sabotage success

11/20/2013

Make the Most of Electric Tracing

The technique offers benefits but demands attention to details

01/02/2014

Match the Flow Meter to the Service

Consider operating conditions not just specifications and price

01/23/2014

Rest Easy With a Good BEDD

A basic engineering data document establishes ground rules.

02/20/2014

Plant Safety: Leaks Don't Lie

Treat them as calls for action against the underlying problem.

03/19/2014

Pumps: Check "Standard Conditions"

Otherwise you risk using the wrong value for density in calculations.

04/08/2014

Carefully Commission Hydrogen Pipe

Safety depends upon scrupulously performing a variety of inspections and tests

06/11/2014

Equipment Maintenance: Savor Statistics

It can help you uncover important insights from your data

08/06/2014

Get Your Head Around Shutoff Head

Specifying control valves that may need to provide tight cutoff requires care

08/20/2014

Protect your electronics

Ignoring exposed electrical boxes can cost you a bundle, says Contributer Dirk Willard, in this month's Field Notes column.

06/06/2007

Field Notes: Don't Know Much Geometry

The cornerstones of chemical engineering are often overlooked. Teaching theory to operators is crucial to safe operations, says Dirk Williard in his monthly Field Notes column.

04/12/2006

Level transmitter — art not science

There is much more to setting up a transmitter than a mere equation. Design and control errors can certainly compromise performance. Follow these simple tricks to get it right.

06/13/2006

Solve the real problem

Sometimes solving a problem causes more harm than good.

05/06/2006

Build reliability in during design

Instrumentation that promises to improve reliability may not always be what they seem. You have to consider whether a site can properly maintain sophisticated instruments.

12/19/2007

It really isn’t your problem

A manager shouldn’t try to be a Mr. Fix-it.

02/05/2008

Stick to the basics

Getting immersed in details can doom a basic design contract to financial failure.

02/13/2008