Get Your Head Around Shutoff Head

Specifying control valves that may need to provide tight cutoff requires care

By Dirk Willard, Contributing Editor

A data sheet for a reactor flow-control valve called for a “shutoff head.” Given that this control valve handled ethylene oxide (EO), a highly volatile and reactive compound, the requirement gave me pause. Addressing it involved more than defining the pump deadhead pressure. Here’re some thoughts to consider.

First, it’s important to understand that a control valve isn’t a shutoff valve. A control valve must provide precise adjustments to flow. Crunching down on the plug to block flow can cause damage. The actuator and linkage of a control valve aren’t designed for tight shutoff; a shutoff valve’s actuator is. If you want to prevent leakage, install a shutoff valve.

Unfortunately, no standards define control-valve shutoff head. A few describe leakage through the body of a valve; this leakage is categorized poorly as Class I-VI in ANSI/FCI 70-2, “Control Valve Seat Leakage.” Valves also leak from their stems. For stem leakage, refer to ISO-15848, “Industrial Valves — Measurement, Test and Qualification Procedures for Emissions – Part 1...” This specification is best because it recommends helium as the test medium. API-622, “Type Testing of Process Valve Packing for Fugitive Emissions,” also describes stem leakage but for methane.

However, we’re concerned about defining the shutoff head for a control valve specification, not leakage. For this, understanding the limits of valve body type is important. Obviously, butterfly valves won’t provide tight shutoff — although I have seen them used where leaking is acceptable, such as where thermal expansion is allowed. Be aware that thermal expansion could cause the valve seat to stretch or dislodge. In this case, the valve itself limits the shutoff head. Butterfly valves are available with shutoff heads of 175 psi and up, but, in practical terms, the limit is more like 50 psi or less. Diaphragm and other soft-seat valves have the same problem. Gate valves, with their exposed seats and metal-on-metal sealing surfaces, are a bad choice. Globe valves, while often most effective for control, are the worst option. Ball and plug valves probably offer the best choice for shutoff.

Lack of mechanical strength is a common problem with soft seats but less of an issue with hard, metal-on-metal seats. Soft seats are best for sealing against streams containing solids, such as slurries. Hard surfaces, polished smooth, work best at high temperatures, above 250°F, where polymers begin to break down or flow; solids quickly ruin polished surfaces. Fluoropolymers can extend the range of soft seats to 350°F. However, hard plastics retain memory and can be scratched just like metal; memory retention gets worse above 200°F. Partially-fluorinated polymers generally outperform polytetrafluoroethylene (PTFE) in fabricated liners but PTFE serves well as sheets. Ceramics offer a useful alternative to metal in erosive environments but not without sacrificing tight shutoff.

Enough about the peripherals, let’s get down to specifications. Several scenarios can define shutoff head: 1) flow provided by a mover, e.g., a pump or compressor; 2) pressure isolation; 3) temperature control; and 4) safety, i.e., prevention of a chemical reaction. In the first case, use the deadhead pressure of the mover. (Deadhead is the extreme left corner on a pump curve.) For a pump, pick the deadhead for the largest impeller possible. For temperature control, use the regulator steam pressure — unless a significant risk is present and the steam is stepped down, in which case use the original pressure. Safety is a tricky subject.

If a chemical such as EO is involved, safety trumps a pump curve. EO leaking past the isolation valves to the reactor could lead to a release or worse. In this situation, as in the others requiring a tradeoff between control and isolation, don’t rely on a control valve for shutoff: put automatic valves upstream and downstream of the control valve for isolation. Install pressure switches and pressure transmitters to monitor thermal expansion and use thermal relief valves to blow expanding liquids back to storage. Both switches and transmitters are valuable because transmitters are limited to <100-ms response time and switches don’t trend.

Lastly, let’s look at actuators. If a control valve is to function as a reliable shutoff valve, a positioner is an absolute necessity. Ideally, use one with a 0–100% position indicator. Specify an open-and-closed position indicator for all automatic valves used for shutoff. Take care in selecting the actuator air pressure and supply; evaluate the pressure reliability before selection; plan for 1 scfm of air per control valve or automatic valve that’s 6 in. or less in size.


dirk.jpgDIRK WILLARD is a Chemical Processing contributing editor. He recently won recognition for his Field Notes column from the ASBPE. Chemical Processing is proud to have him on board. You can e-mail him at dwillard@putman.net

More from this perspective...

Title

Safety Statistics Can Get You into a Scrape

Focusing on minor accidents can foster false perceptions.

12/03/2009

Take the Write Steps for Career Advancement

The ability to compose clear and effective documents is an important asset.

03/03/2010

Treat Rules of Thumb Right When Measuring

These rules can save time but require a strong dose of skepticism.

04/01/2010

Expand Your Plant Not Your Problems

Careful project planning and good communications with vendors can avoid hassles.

05/10/2010

Use Ergonomics To Improve Safety

During design always consider ease of construction and use.

06/03/2010

Size Pumps Like a Pro

Use a step-by-step process to avoid pitfalls.

07/01/2010

Watch Out When Job Hunting

Some simple steps can avoid risks and pitfalls.

07/29/2010

Avoid Surprises During Pump Startup

A well-thought-out approach can eliminate potential problems.

08/26/2010

Keep Confined Space Work Safe

Rigorous attention to detail is essential to minimize risks and enhance response.

09/27/2010

Weak Oversight Can Doom a Project

Don't timidly accept whatever a contractor proposes.

11/02/2010

Do Your Level Best

Level control with dP transmitters appears simple but really isn't.

11/29/2010

Silence Kills

Foster an atmosphere where workers speak up about concerns.

09/26/2011

Don't Push the Envelope

Take a sensible approach to avoid ignition dangers.

05/05/2011

Don't Devalue Isometrics

They sometimes can tell you a lot more than P&IDs

10/19/2011

Don't Zone Out On Area Classifications

Electrical ratings must start with analysis of chemicals present.

04/06/2011

Heat Exchangers -- Keep Out of Hot Water

Some simple steps can ease heat exchanger commissioning.

02/03/2011

Know Your Rights

Intellectual property agreements can pose significant concerns.

03/03/2011

Stop Loops Driving You Round the Bend

Practical pointers trump educators' edicts for real-world process control.

01/12/2011

Savor Construction Sites

But make sure the excitement remains enjoyable.

11/17/2011

Succeed at Process Troubleshooting

Take advantage of five easy techniques to find the root cause of problems.

08/08/2011