Re: Number of wires required for RTD sensors
27 June 2007 at 1:29pmThis answer was provided by Robert L. Heider, Lecturer and Adjunct Professor for the Department of Energy, Environmental & Chemical Engineering at Washington University in St. Louis.
The use of either 3- or 4-wire elements depends on the input circuit used. Three leads are used where the element is one leg of a bridge circuit. One of the common leads is connected to the voltage source. This balances the lead resistance, assuming the wires are of the same resistance. Four-wire elements are used where the source is a constant current generator. Two of the leads are used to power the element and the remaining two are used to measure the voltage drop across the element. The lead wire resistances are much lower than the input impedance of the voltage measuring input circuit. Two-wire element creates error in the measurement, the lead wires are not balanced. In the absence of any information from the transmitter specifications, refer to the following table:
Deflection type instruments Length, feet Wire Size B&S Gage 250 or less 20 or larger 400 or less 18 or larger 625 or less 16 or larger 1000 or less 14 or larger Null bridge 1500 or less 16 or larger References
McMillan, G. K., Process/Industrial Instruments and Controls Handbook, New York, McGraw-Hill, 1999, Section 4-24
Considine, D. K., Process/Industrial Instruments and Controls Handbook, New York, McGraw-Hill, 1957, Section 2-57