Home » What safety requirements are necessary for a fuel switchover on a furnace?

Print page

What safety requirements are necessary for a fuel switchover on a furnace?

Q: We have a natural draft furnace designed to use the fuels hydrogen, natural gas and LPG. In the event of a fuels changeover while the furnace is on-line, what are all the safety instruments and controls that should be considered to safeguard the equipment and operating personnel?

A: You say that the natural draft furnace is already designed for H2, NG and LPG.  So it is safe to assume that the furnace already has flame safety equipment for each individual gas train.
 
Also, it is assumed that the injection lances are separate for each of the fuels, since the switchover will be done on-line.  So the only adjustment that is required is the amount of combustion air.  The combustion air should be adjusted depending on the amount of the fuel used.  The controller for combustion air should be programmed accordingly.

Here are more of the latest questions on: Combustion

Can you explain buoyant thermal force?
In flare tips, we know at minimum flow at low velocity and with no wind the flame of the flare tip is almost vertical. If the wind velocity increases the flame goes horizontal.

We need to explain to our client why this happens. We only know this is a phenomenon called buoyant thermal force, but we do not know the background and governing equations of this behavior. Can you explain?

Can you suggest routine checks for a furnace?
We have a Foster-Wheeler-designed furnace for reforming natural gas. The furnace is induced draft and has two chambers. Can you suggest routine checks an operations engineer must do during normal operation?

Is soot-blowing still applicable?
Is soot-blowing still applicable when natural and or fuel gas with <0.05 wt percentage H2S and <0.1 C6+ is being fired? To me this is a waste of money if the frequency is once a day. On other furnaces and boilers the convection sections are being cleaned every five years with the same fired fuel. I need to convince the owners.

What safety requirements are necessary for a fuel switchover on a furnace?
We have a natural draft furnace designed to use the fuels hydrogen, natural gas and LPG. In the event of a fuels changeover while the furnace is on-line, what are all the safety instruments and controls that should be considered to safeguard the equipment and operating personnel?

Is there a formula to calculate how much wood was present prior to burning?
Is there a formula for calculating remaining wood as residue to calculate how much wood was present prior to being burned? And if so, could the formula be used on remaining wood ash residue that has been exposed to the elements for seven months?

Back to Ask the Experts

More content on this topic:

Featured Sponsor