Is there a flow meter that will be reliable, even with moderate particulate in the air stream?
Q: One of my processes has a dust-collection line to eliminate nuisance dust. The same line is tapped for a supporting process in the room. The problem we have experienced is that the dust collection adversely affects the product yield if flow rates are too high. We don't have a way of quantifying an acceptable flow range. I would like to install a flow meter so we can determine such a range and make it part of the operation procedure. The line is about 4 inches in diameter. I've looked at a few flow meters, but would like your thoughts on which type would be best suited for this application. I want to find something that will be reliable, even with moderate particulate in the air stream. Of course, the more economical the solution, the better the chance it will have of happening.
A: A flow nozzle or flow venturi (differential head meter) with a multivariable transmitter (d/p, pressure and temperature) would provide a mass flow with a turndown of 5:1. You could use just a d/p transmitter to get volumetric flow. In either case, the sensing lines need to be purged with an inert gas such as nitrogen to keep particulates out of the lines. I favor a flow nozzle or venturi over an orifice plate to avoid the problems of orifice edge wear and buildup of particulates on the plate. Also, the straight run requirements are less and the turndown (rangeability) and accuracy is slightly better.
If much greater flow turndown (rangeability) or accuracy is needed, you could go to a Coriolis flow meter, but this meter is much more expensive than a differential head meter for your line size. Additionally, a Coriolis meter requires relatively high gas pressures (high gas densities) to perform properly and the pressure drop across the meter is much larger than the pressure drop across a flow nozzle or venturi tube.
Here are more of the latest questions on: Instrumentation and Control
Can you explain a split range controller?
Regarding split range controller:
- Is it normal to have a control valve with two different sizes?
- Why use a split range controller and where can we it?
- My application: I am planning to use at outlet of condenser. The outlet will have condensate liquid and non-condensate vapor. Will it work here?
Can you explain linearity and accuracy of flowmeters?
I am confused on linearity and accuracy of flowmeters such as oval meters. In some references they are mentioned as the same but in some others they are not the same. Should I only rely on linearity for selection for measuring custody transfer or another flowmeter characteristic?
Can you recommend a flowmeter?
We are going to install a flowmeter for lube oil loading as custody transfer. The flowrate may alter between 140-280 CMH (two-speed motor) having viscosity 150cSt at 40C. Simple installation and setting up on the line and reasonable cost as well as pressure drop are preferred. The pump can generate 8barg pressure. What would be the recommended flow measuring type to support the requested service?
Where should I install the control valve on the hot oil line?
I am going to use hot oil for heating a process in a jacketed vessel and I am going to make a control loop for controlling the vessel content. The hot oil enters at the bottom of the jacket and exits from the top. The control elements are RTD, controller, and control valve. My question: Where should I install the control valve on the hot oil line? Is it up stream or down stream of the vessel?
Why is there a discrepancy of solids at sampling points?
Ours is a fertilizer industry and within the premises we transfer phosphoric acid from the phosphoric acid production facility to the fertilizer production facility. The distance of the pipeline might be around 400m but the difference in issue and receipts generally comes out to be 100s of tons per day. Can you tell me what could be the possible problem? Other info required:
- Phosphoric acid has around 5% solids
- Sampling point in phosphoric acid tank is at the bottom
- Sampling point in the fertilizer plant is at a higher level(25 ft) and is preceded by a lot of bends.
Print page