Home » Automation IT » What is the cause of high silica and aluminum?
What is the cause of high silica and aluminum?
Q: The result of a residue analysis from the bottom of the furnace is: Na 2.61%; Mg 1.39%; Al 31.34%; Si 48.16%; Ca 9.17%; V 1.59%; Cr 0.32%; and Fe 5.42%. The residue is a form of glass contaminated with trace of metallic elements. We fire fuel oil No. 5 with high ash content. We need your comments and suggestions on the above and what is the cause of the high silica and aluminum.
A:
It appears the ash from the No. 5 fuel oil is ending up at the bottom of the furnace in the form of glass.
I would recommend that the user do a metal analysis of the ash in No. 5 fuel oil to determine how much of the ash in fuel oil is ending up in the glass.
The high amount of silica and alumina in the alumina is most probably from the furnace refractory. Loss of the furnace refractory usually ends up in the glass residue at the bottom.
Normal analysis of No. 5 fuel oil is:
Carbon – 88.7%
Hydrogen – 10.7%
Sulfur – 0.57%
Ash – 0.02%
Moisture – 0.4%
The ash present in the No. 5 fuel will cause fouling in the boiler. The extent of the fouling will depend on the quantity and composition of the ash in the fuel oil and the design of the boiler.
Here are more of the latest questions on: Combustion
Can you explain buoyant thermal force?
In flare tips, we know at minimum flow at low velocity and with no wind the flame of the flare tip is almost vertical. If the wind velocity increases the flame goes horizontal.
We need to explain to our client why this happens. We only know this is a phenomenon called buoyant thermal force, but we do not know the background and governing equations of this behavior. Can you explain?
Can you suggest routine checks for a furnace?
We have a Foster-Wheeler-designed furnace for reforming natural gas. The furnace is induced draft and has two chambers. Can you suggest routine checks an operations engineer must do during normal operation?
Is soot-blowing still applicable?
Is soot-blowing still applicable when natural and or fuel gas with <0.05 wt percentage H2S and <0.1 C6+ is being fired? To me this is a waste of money if the frequency is once a day. On other furnaces and boilers the convection sections are being cleaned every five years with the same fired fuel. I need to convince the owners.
What safety requirements are necessary for a fuel switchover on a furnace?
We have a natural draft furnace designed to use the fuels hydrogen, natural gas and LPG. In the event of a fuels changeover while the furnace is on-line, what are all the safety instruments and controls that should be considered to safeguard the equipment and operating personnel?
Is there a formula to calculate how much wood was present prior to burning?
Is there a formula for calculating remaining wood as residue to calculate how much wood was present prior to being burned? And if so, could the formula be used on remaining wood ash residue that has been exposed to the elements for seven months?