Choosing Dry or Wet Reference Legs
Q: In the d/p Level transmitters, what is your criteria to choose dry or wet reference legs? I now that wet leg is used for fluids that condensate. How do you check if a fluid condensates? By checking the vapor pressure? Is it only for ambient temperatures?
A:
There are many variables that need to be considered.
They include:
· Ambient temperature range
· Temperature range of liquid in the tank
· Vapor pressure and/or temperature at which the liquid will condense and freeze in the low pressure leg
If you want to keep the leg full, connect a 1 gph purge meter to the bottom of the low pressure leg.
If the liquid in the tank has water in it, water can be used as the purge liquid; however, if the tank is in a location where the ambient temperature goes below 0 degrees C, the leg must be traced and insulated. If the tracing if too extensive, the purge water will begin to boil and the level transmitter will give a false reading.
If the tank has an organic liquid in it that could be used as the purge liquid provided, it doesn't freeze or vaporize too quickly.
Better yet, move the tank to a warm climate like SW Florida. Nothing freezes here. Besides, the way the economy is going, I could use a part time job.
A better or easier method might be to keep the low level leg empty.
If the liquid vaporizes at a relatively low temperature, steam tracing the line works.
Or, purge the line with Nitrogen or some other inert gas.
Another trick is to connect the low side of the d/p to a pipe well above the tank; so that no liquid can get into the leg.
If none of these methods work, put chemical seals on both sides of the d/p transmitter.
Or, don't use a d/p transmitter.
There are capacitance probes, nuclear, sonar,.........................
In the old days, we got a guy with a long stick to put it and his head in the tank. Then he could phone the reading back to the control room. If the operator in the control room didn't like the answer, he would tell the field operator to get a different reading. This tried and true method works as long as too many operators don't fall off the tank ladder or get poisoned from the tank fumes.
Stan Weiner contributed to this answer. And did you know that he and Greg McMillan write a column each month in our sister publication Control Global? You can view the current Control Talk column at http://www.controlglobal.com/voices/mcMillan_weiner.html.
Here are more of the latest questions on: Instrumentation and Control
Can you explain a split range controller?
Regarding split range controller:
- Is it normal to have a control valve with two different sizes?
- Why use a split range controller and where can we it?
- My application: I am planning to use at outlet of condenser. The outlet will have condensate liquid and non-condensate vapor. Will it work here?
Can you explain linearity and accuracy of flowmeters?
I am confused on linearity and accuracy of flowmeters such as oval meters. In some references they are mentioned as the same but in some others they are not the same. Should I only rely on linearity for selection for measuring custody transfer or another flowmeter characteristic?
Can you recommend a flowmeter?
We are going to install a flowmeter for lube oil loading as custody transfer. The flowrate may alter between 140-280 CMH (two-speed motor) having viscosity 150cSt at 40C. Simple installation and setting up on the line and reasonable cost as well as pressure drop are preferred. The pump can generate 8barg pressure. What would be the recommended flow measuring type to support the requested service?
Where should I install the control valve on the hot oil line?
I am going to use hot oil for heating a process in a jacketed vessel and I am going to make a control loop for controlling the vessel content. The hot oil enters at the bottom of the jacket and exits from the top. The control elements are RTD, controller, and control valve. My question: Where should I install the control valve on the hot oil line? Is it up stream or down stream of the vessel?
Why is there a discrepancy of solids at sampling points?
Ours is a fertilizer industry and within the premises we transfer phosphoric acid from the phosphoric acid production facility to the fertilizer production facility. The distance of the pipeline might be around 400m but the difference in issue and receipts generally comes out to be 100s of tons per day. Can you tell me what could be the possible problem? Other info required:
- Phosphoric acid has around 5% solids
- Sampling point in phosphoric acid tank is at the bottom
- Sampling point in the fertilizer plant is at a higher level(25 ft) and is preceded by a lot of bends.
Print page