Bringing exposed piping into SPCC compliance
Q: I am working to bring a co-generation plant into compliance with federal SPCC regulations. We have issues regarding exposed piping in areas where secondary containment and/or drainage controls are not practical. Are there double-walled piping systems that are suitable for diesel fuel but that can be used above-ground? What would be the best material for this application, taking into account UV exposure, durability, leak detection and maintenance requirements?
A:
There are two issues at work here. The first is the likelihood of spills from that source and the second is the regulations. The question caused me to go back and perform a memory check with regard to the regulations, and at one time, not all facilities were required to have an SPCC Plan if they did not have any likelihood that they could have a spill. (See Section 112.3 for requirements ). The test is good engineering practice. That doesn't necessarily require a double wall piping system because those systems are not necessarily trouble free, and are often a pain in the neck to install. Depending upon the assessment of potential damage, I might recommend a sheet metal gutter system, suitably caulked to prevent leaks, which is installed under the portions of the exposed piping of concern. The gutters can be drained to a small containment basin locally installed and monitored, and the piping, if it is pressure checked periodically (say once per year or as required) should last a long time. If there is concern, a catch basin may be easier to install than trying to drain the piping all the way back to an containment area. If there is concern about it, install an oil monitoring device (conductivity probe) or even a water level meter would work so that you have time to get to the problem and check it when the level alarm goes off.
As far as materials of construction, there are no really bad materials. PVC will work just fine as will sheet metal. Again, if it were me, and the piping were fairly standard, I'd use a nominal 1/2 pipe installation set just below the pipe as an oil trap. Support it with straps and hangars as you would, but drain it to somewhere you can catch the oil. The point is to give yourself a fighting chance rather than to make it idiot proof. (When you make something fool proof, Nature invents an improved fool). The point is that visual inspection is still your best bet for leak control, and if you provide a catchment system, almost any catchment system beneath the pipe, that should be adequate. It depends upon what the certifying engineer considers "Good Engineering Practice" as defined by Section 112.7 of the regulations.
To summarize: 1) use a half pipe of almost anything and install it beneath the existing pipe in the area of concern. If the distance is too great, drain it to a catch basin which you visually inspect each time it rains. The catchment piping can be anything which does not leak, but I'd probably use PVC of a size large enough to cover the oil carrying pipe flanges with some room to spare. So if you have a 4" pipe, your final drainage pipe may be 8" - 10" so that it can go around the pipe flanges, or 6-8 inches if the pipe is continuously welded.
Here are more of the latest questions on: Environmental Protection
Can our calcium carbonate "waste" be utilized in other industries so we can divert it from landfills?
I work for a major sugar producer. As part of our process, calcium carbonate is created at a refinery that utilizes a process called carbonization for primary purification. In this process lime (calcium oxide or CaO) and carbon dioxide (CO2) are proportionally added and a chemical reaction takes place. A calcium carbonate (CaCO3) precipitate is formed as a result, which captures colorant between the CaCO3 crystals and this is subsequently filtered out, desweetened, and partially dried.
Currently we dispose of millions of pounds of this calcium carbonate "waste" each year. We would like to know if this material can be utilized in other industries so we can divert it from landfills to be recycled. Please advise if you know of any outlets for this material. Analytic testing results can be provided if needed.
What is causing the gummy mess in the fermentation process?
We are facing a gummy fermented mash in our fermentation section using sugarcane molasses as feedstock. What is the reason of formation of gum in fermentation? How can we overcome the gum? Is there a method for determining the amount of the gum in mash?
What impact does ethanol have in the operation of the wastewater treatment plant?
I'm looking for information regarding refineries' experiences handling ethanol-gasoline vapors from truck loading racks in their flare system. Also, the impact ethanol has in the operation of the wastewater treatment plant. In some systems, these vapors will mix with water (in headers, FGR units, Flare KO drums, sour water stripping units, etc.) and will end up in wastewater units. What steps have been taken to manage this situation?
Could you recommend a good method for separating exhaust?
We have an exhaust stream that includes CH4, CO2, CO, H2O. I want to separate CH4 and reuse it in the furnace. Could you recommend a good method for separation?
Is there a better chemical to use as an anti-foaming agent?
We have a problem with excess foam generated in our primary rinse out conveyor. The rinser uses water to remove PVA film left over by a decorative film dipping process (water transfer printing).
We have tried an anti-foaming product with Polydimethylsiloxane, but we are still having to use far more than the recommended amount for the two 100-gallon tanks.
Is there a better chemical to use as an anti-foaming agent or can the foam be reduced mechanically?
Print page