Control Valve Sizing
Q: I would like to know, why reducer and expander is provided in inlet and outlet line of Control valve? Is there any perticular reason for it?
A:
The line should be determined by an economic pipe sizing program.That will make the fluid velocity in the pipe stay within certain boundaries (not too slow or not too fast). If the flow is too slow, the pipe is probably larger than necessary which is more expensive to purchase and install. If the pipe is too small, the high fluid velocity will be noisy and probable erode the piping system.
The control valve needs to be sized using a pressure drop that is about equal to the system pressure drop (pipe friction + filters + heat exchangers ++). If the valve is sized with an arbitrary pressure drop of 10 pounds, it is a crap shoot as to it's ability to control. If the valve pressure drop is too low, the system will control the fluid flow, not the valve. If the pressure drop is too high, the valve may be much smaller than the pipe, noisy and probably wear out in a relatively short period of time. Also, the small valve, relative to the pipe size, may be under a great deal of stress when the pipe expands and contracts due to temperature changes.
So, in my vast experience as a valve sizer, they are usually smaller than the pipe. In order to get the valve to fit in a larger size pipe, you need 2 pipe reducers, one on each side.
If the valve and pipe are the same size, something is wrong. If the valve is larger than the pipe, everything is wrong and somebody spent a significant amount of money for a large valve and 2 reducers.
Here are more of the latest questions on: Instrumentation and Control
Can you explain a split range controller?
Regarding split range controller:
- Is it normal to have a control valve with two different sizes?
- Why use a split range controller and where can we it?
- My application: I am planning to use at outlet of condenser. The outlet will have condensate liquid and non-condensate vapor. Will it work here?
Can you explain linearity and accuracy of flowmeters?
I am confused on linearity and accuracy of flowmeters such as oval meters. In some references they are mentioned as the same but in some others they are not the same. Should I only rely on linearity for selection for measuring custody transfer or another flowmeter characteristic?
Can you recommend a flowmeter?
We are going to install a flowmeter for lube oil loading as custody transfer. The flowrate may alter between 140-280 CMH (two-speed motor) having viscosity 150cSt at 40C. Simple installation and setting up on the line and reasonable cost as well as pressure drop are preferred. The pump can generate 8barg pressure. What would be the recommended flow measuring type to support the requested service?
Where should I install the control valve on the hot oil line?
I am going to use hot oil for heating a process in a jacketed vessel and I am going to make a control loop for controlling the vessel content. The hot oil enters at the bottom of the jacket and exits from the top. The control elements are RTD, controller, and control valve. My question: Where should I install the control valve on the hot oil line? Is it up stream or down stream of the vessel?
Why is there a discrepancy of solids at sampling points?
Ours is a fertilizer industry and within the premises we transfer phosphoric acid from the phosphoric acid production facility to the fertilizer production facility. The distance of the pipeline might be around 400m but the difference in issue and receipts generally comes out to be 100s of tons per day. Can you tell me what could be the possible problem? Other info required:
- Phosphoric acid has around 5% solids
- Sampling point in phosphoric acid tank is at the bottom
- Sampling point in the fertilizer plant is at a higher level(25 ft) and is preceded by a lot of bends.
Print page