Number of wires required for RTD sensors
Q: What is the distance a signal conditioning transmitter will reach with a 2-wire RTD sensor? When is it best to use a 3- and 4-wire RTD?
A: This answer was provided by Robert L. Heider, Lecturer and Adjunct Professor for the Department of Energy, Environmental & Chemical Engineering at Washington University in St. Louis.
The use of either 3- or 4-wire elements depends on the input circuit used. Three leads are used where the element is one leg of a bridge circuit. One of the common leads is connected to the voltage source. This balances the lead resistance, assuming the wires are of the same resistance. Four-wire elements are used where the source is a constant current generator. Two of the leads are used to power the element and the remaining two are used to measure the voltage drop across the element. The lead wire resistances are much lower than the input impedance of the voltage measuring input circuit. Two-wire element creates error in the measurement, the lead wires are not balanced. In the absence of any information from the transmitter specifications, refer to the following table:
| Deflection type instruments | |
| Length, feet | Wire Size B&S Gage |
| 250 or less | 20 or larger |
| 400 or less | 18 or larger |
| 625 or less | 16 or larger |
| 1000 or less | 14 or larger |
| Null bridge | |
| 1500 or less | 16 or larger |
References
McMillan, G. K., Process/Industrial Instruments and Controls Handbook, New York, McGraw-Hill, 1999, Section 4-24
Considine, D. K., Process/Industrial Instruments and Controls Handbook, New York, McGraw-Hill, 1957, Section 2-57
Here are more of the latest questions on: Instrumentation and Control
Can you explain a split range controller?
Regarding split range controller:
- Is it normal to have a control valve with two different sizes?
- Why use a split range controller and where can we it?
- My application: I am planning to use at outlet of condenser. The outlet will have condensate liquid and non-condensate vapor. Will it work here?
Can you explain linearity and accuracy of flowmeters?
I am confused on linearity and accuracy of flowmeters such as oval meters. In some references they are mentioned as the same but in some others they are not the same. Should I only rely on linearity for selection for measuring custody transfer or another flowmeter characteristic?
Can you recommend a flowmeter?
We are going to install a flowmeter for lube oil loading as custody transfer. The flowrate may alter between 140-280 CMH (two-speed motor) having viscosity 150cSt at 40C. Simple installation and setting up on the line and reasonable cost as well as pressure drop are preferred. The pump can generate 8barg pressure. What would be the recommended flow measuring type to support the requested service?
Where should I install the control valve on the hot oil line?
I am going to use hot oil for heating a process in a jacketed vessel and I am going to make a control loop for controlling the vessel content. The hot oil enters at the bottom of the jacket and exits from the top. The control elements are RTD, controller, and control valve. My question: Where should I install the control valve on the hot oil line? Is it up stream or down stream of the vessel?
Why is there a discrepancy of solids at sampling points?
Ours is a fertilizer industry and within the premises we transfer phosphoric acid from the phosphoric acid production facility to the fertilizer production facility. The distance of the pipeline might be around 400m but the difference in issue and receipts generally comes out to be 100s of tons per day. Can you tell me what could be the possible problem? Other info required:
- Phosphoric acid has around 5% solids
- Sampling point in phosphoric acid tank is at the bottom
- Sampling point in the fertilizer plant is at a higher level(25 ft) and is preceded by a lot of bends.
Print page