Cumulative flow measurement instrumentation

Q: What is the instrument that can take a cumulative flow measurement of an effluent slurry containing fibers? I am required to measure the quantum of effluent that I send to a common effluent treatment plant. The effluent was generated by the dying operation of jute yarn and it contains jute fibers. Vanes of the flow meters (water meter) stops its running by these fibers. Is there is any electronic device like the energy meter (that is used to measure power consumption) available? Can a mass flow meter be used in this application?

A: If a volumetric flow measurement is sufficient, a correctly sized magnetic flow meter should be able to provide a repeatability of 0.25% of rate. Options exist for the materials used for the wall and electrodes if the fibers are abrasive. If you need much better performance, the considerably more expensive Coriolis mass flow meter has a repeatability of 0.04% of rate and offers a true mass flow, density and percent solids measurement. Again, materials of construction must be reviewed for abrasion.

To get a cumulative (total) flow, the measurement signal of flow rate is sent to a flow integrator (totalizer) that has a zero drop-out feature where the flow reading is zeroed out when the flow drops below a low flow limit. This drop-out feature is important to prevent the integration of noise and negative flow signals when the signal is below the low flow limit of the meter (e.g. signals below 5% for a magnetic flow meter and 1% for a Coriolis flow meter).

Here are more of the latest questions on: Instrumentation and Control

Can you explain a split range controller?
Regarding split range controller:

  1. Is it normal to have a control valve with two different sizes?
  2. Why use a split range controller and where can we it?
  3. My application: I am planning to use at outlet of condenser. The outlet will have condensate liquid and non-condensate vapor. Will it work here?

Can you explain linearity and accuracy of flowmeters?
I am confused on linearity and accuracy of flowmeters such as oval meters. In some references they are mentioned as the same but in some others they are not the same. Should I only rely on linearity for selection for measuring custody transfer or another flowmeter characteristic?

Can you recommend a flowmeter?
We are going to install a flowmeter for lube oil loading as custody transfer. The flowrate may alter between 140-280 CMH (two-speed motor) having viscosity 150cSt at 40C. Simple installation and setting up on the line and reasonable cost as well as pressure drop are preferred. The pump can generate 8barg pressure. What would be the recommended flow measuring type to support the requested service?

Where should I install the control valve on the hot oil line?
I am going to use hot oil for heating a process in a jacketed vessel and I am going to make a control loop for controlling the vessel content. The hot oil enters at the bottom of the jacket and exits from the top. The control elements are RTD, controller, and control valve. My question: Where should I install the control valve on the hot oil line? Is it up stream or down stream of the vessel?

Why is there a discrepancy of solids at sampling points?
Ours is a fertilizer industry and within the premises we transfer phosphoric acid from the phosphoric acid production facility to the fertilizer production facility. The distance of the pipeline might be around 400m but the difference in issue and receipts generally comes out to be 100s of tons per day. Can you tell me what could be the possible problem? Other info required:

  1. Phosphoric acid has around 5% solids
  2. Sampling point in phosphoric acid tank is at the bottom
  3. Sampling point in the fertilizer plant is at a higher level(25 ft) and is preceded by a lot of bends.
Could this be an issue with the sampling points or the data analysis?

Back to Ask the Experts

More content on this topic:

Featured Sponsor