Unknown pump performance increase

Q: I have conducted an annual firewater pump test and I am puzzled with the pump curve result that I have obtained. The pump is from the centrifugal pump type and utilizing sea water as the fluid service. I am supposed to compare the pump curve result with the previous year result and I have found out that the pump performance has improved significantly compared to the previous year. This should be good news, but the problem is no improvement work has been done for the pumps for the past two years and theoretically the pump should either maintain its last performance or continue to degrade. I have used a different test procedure from the previous test, in which the main difference is the location of the water discharge. Does the location of the water outlet affect the pump discharge pressure? Will the upstream pressure drop affect the pump discharge pressure? The discharge pressure that I am referring to is the pressure obtained from the pressure gauge located as soon as the pump discharges and not at the end of the pipeline.

A: When the location of the water discharge is changed in a pumping system, that changes the system, which will, in turn, change the point on the performance curve at which the pump will operate. The comment was made that the pump performance improved over the previous year, but we don’t know how it changed. We will assume it means that the flow rate has increased. This would be perfectly normal if the discharge pressure that the pump is required to produce is lower than it was on the previous test.

The rule to remember is that a centrifugal pump is a slave to the system, and will only do what the system demands. Therefore if the system requires a lower output pressure from the pump, then the pump operation will move further out on its curve and deliver a higher flow rate.

Here are more of the latest questions on: Pumps

Why are we experiencing anti-rotating device failures at an alarming rate?
We have three circulating water vertical pumps and we are experiencing anti-rotating device failures at an alarming rate. The discharge line is 72 inches. All the parameters have been checked and we are still clueless of the problem. Pump Detail Equipment description: Circulating Water Pump
Equipment Tag No. : CW-PP-002 (A/B/C)
Type: Vertical Flow Sump Pump
Model: 1800HV
Head: 17m
Capacity: 17280 m3/h
Shaft power: 971 kW
Speed: 495 rpm
Pump height:10m
Weight (pump): 30 ton
Weight (motor): 20 ton
Manufacturer: Shenyang Pump Manufactory, China

Is dynamic balancing important?
I have always been told that dynamic balancing is not as critical on impellers because as soon as the impeller is loaded, the water causes hydraulic imbalance. We have always balanced them down to NEMA standards anyway, but it would be nice to know for sure.

Does the velocity in the suction line need to be maintained?
In a new installation, the supplier has erected a suction pipe of 3 inches connected to suction nozzle of 4 inches in the centrifugal pump for slurry application. The general engineering practice says the suction pipe should be the same or one size larger than the suction nozzle of the pump. As per supplier, this arrangement was made to maintain slurry speed of >1.5m/sec. With this condition, we are having frequent seal failures. Please suggest whether this type of suction pipe sizing is acceptable. And is it required to maintain slurry speed in the suction side as given by supplier?

What are the disadvantages of putting a strainer on the discharge of a pump?
What are the disadvantages of putting a strainer on the discharge of a pump?

What is causing the strainer to choke?
We have an ammonia recovery system at our ammonia plant. Ammonia is recovered in a scrubber operating at 105 Kg/cm2 with lean water. Water is pumped through a PD pump. Basket type strainer is installed at pump suction line in vertical position. Chocking problem is frequently observed with this strainer with algae layer due to which pump flow reduces to minimum. What do you recommend?

Back to Ask the Experts

More content on this topic:

Featured Sponsor