Control pressure at discharge

Q: I have five pumps running parallel, transferring water. Due to pressure fluctuation at discharge, which depends on the flow requirements of the user, I am planning to install a pressure control valve at the pump discharge to keep the pump running at an optimum condition. My candidate is a globe valve, but because the line size is quite big (14 in.), the globe valve is not adequate. An engineering consultant suggested a butterfly type. According to past experience, using this kind of valve is not effective for pressure control. What kind of valve is best for a 14-in discharge?

A: Mark Coughran, senior control engineering consultant, Emerson Process Management, provided this answer.

I have seen problems in the past with butterfly valves on large water lines. See, for example, page 10.54 of Process/Industrial Instruments and Control Handbook, 5th edition, McGraw-Hill. However, things have improved since then in the valves, actuators, positioners and application software.

The problems were typically caused by a combination of factors:

  1. wrong size of valve; valve diameter = pipe diameter, giving high process gain at low travels and low process gain at high travels;
  2. butterfly disk shape contributing to a poor installed flow characteristic;
  3. backlash in the disk-to-shaft and shaft-to-actuator connections and inside the actuator;
  4. poor performance from the valve positioner;
  5. installed torque not properly accounted in selection of the actuator

Today, control valve vendors offer the following:

  1. valve sizing software that predicts the installed flow characteristic so that you can see your controller will be able to handle the flow vs. output curve;
  2. butterfly valves with disk shapes giving more favorable flow and torque characteristics;
  3. zero-backlash connections inside the valve, the actuator and the connection of the valve to the actuator;
  4. valve positioners that respond to 0.1% signal changes in less than one second;
  5. actuator sizing software that predicts the installed torque.

Globe valves typically are too expensive for large process water lines. Your control valve vendor should be able to provide test data on modern butterfly control valves (valve + actuator + positioner) in similar applications. If not, consider a segmented ball valve whose size will probably be smaller than the pipe diameter.  On a 14-in. line, this should give a good flow characteristic, reasonable actuator size and dead band less than 0.3% — for much lower cost than a globe valve.

Next, you should think about the control strategy.  At a minimum, use a controller tuning method that does not oscillate but responds at your required speed, such as Lambda tuning. If you need to control the five lines separately, there will be interaction and balancing concerns. The options range from individual PID controllers to a multivariable controller. All the options are easy to configure and tune in a modern DCS.

Here are more of the latest questions on: Instrumentation and Control

Can you explain a split range controller?
Regarding split range controller:

  1. Is it normal to have a control valve with two different sizes?
  2. Why use a split range controller and where can we it?
  3. My application: I am planning to use at outlet of condenser. The outlet will have condensate liquid and non-condensate vapor. Will it work here?

Can you explain linearity and accuracy of flowmeters?
I am confused on linearity and accuracy of flowmeters such as oval meters. In some references they are mentioned as the same but in some others they are not the same. Should I only rely on linearity for selection for measuring custody transfer or another flowmeter characteristic?

Can you recommend a flowmeter?
We are going to install a flowmeter for lube oil loading as custody transfer. The flowrate may alter between 140-280 CMH (two-speed motor) having viscosity 150cSt at 40C. Simple installation and setting up on the line and reasonable cost as well as pressure drop are preferred. The pump can generate 8barg pressure. What would be the recommended flow measuring type to support the requested service?

Where should I install the control valve on the hot oil line?
I am going to use hot oil for heating a process in a jacketed vessel and I am going to make a control loop for controlling the vessel content. The hot oil enters at the bottom of the jacket and exits from the top. The control elements are RTD, controller, and control valve. My question: Where should I install the control valve on the hot oil line? Is it up stream or down stream of the vessel?

Why is there a discrepancy of solids at sampling points?
Ours is a fertilizer industry and within the premises we transfer phosphoric acid from the phosphoric acid production facility to the fertilizer production facility. The distance of the pipeline might be around 400m but the difference in issue and receipts generally comes out to be 100s of tons per day. Can you tell me what could be the possible problem? Other info required:

  1. Phosphoric acid has around 5% solids
  2. Sampling point in phosphoric acid tank is at the bottom
  3. Sampling point in the fertilizer plant is at a higher level(25 ft) and is preceded by a lot of bends.
Could this be an issue with the sampling points or the data analysis?