Don't Zone Out On Area Classifications

Electrical ratings must start with analysis of chemicals present.

By Dirk Willard, Contributing Editor

2 of 2 1 | 2 > View on one page

Determining whether a chemical is a hazard is the most difficult challenge in EAC work. Here're some general guidelines for classification: 1) only consider NFPA-30 Class I liquids -- Class II and Class III liquids don't produce enough vapor, unless heated; 2) treat a fire danger of at least 3 in an NFPA diamond (refer to NFPA-704) as Class I; 3) categorize mixtures with >30% H2 by volume as Group B (API-500, 5.5.5) and mixtures with >25% H2S as Group C (API-500, 5.5.4) -- NFPA-497 Annex B provides a rule for estimating the NEC group for mixtures of vapors or gases but it doesn't work for H2 and H2S; 4) when in doubt about the chemistry use the worst case in evaluating a hazard; and 5) if you can't measure the molecular weight (MW) of a complex organic, you can get a good estimate for n-alkanes with MWs from 80 to 1,400 via the equation in "Select the Right Hydrocarbon Molecular Weight Correlation" by Donald Schneider of Stratus Engineering: MW = 3.3955×10-15Tbf 6 - 1.2416×10-11Tbf5 + 1.8256×10-8Tbf4 - 1.3234×10-5Tbf3 + 5.2285×10-3Tbf2 – 0.741692Tbf + 116.19, where Tbf is the boiling point.

EAC is based on the auto-ignition temperature (AIT) -- the minimum temperature at which a combustible material will burst into flame without an external ignition source. AITs reported in MSDSs often aren't tested for the particular mixture but reflect testing of a pure compound. There are no mixing rules for the AIT, which severely handicaps studies. Use the following simplification if no other data are available: for compositions containing compounds with MW exceeding 50 use AIT = 280°C; for others, use 200°C.

In later columns, I'll discuss enclosures, preparation of EAC drawings, defining envelopes and remediation.


DIRK WILLARD is a Chemical Processing Contributing Editor. You can e-mail him at dwillard@putman.net

2 of 2 1 | 2 > View on one page

Join the discussion

We welcome your thoughtful comments. Please comply with our Community rules.
All comments will display your user name.

Want to participate in the discussion?

Register for free

Log in for complete access.

Comments

  • Class II is for combustible dusts and Class III is for combustible fibres and flyings, NOT liquids as stated in this article.

    Reply

  • Never mind that's for NFPA-30 classes of liquids not NEC area classes.

    Reply

RSS feed for comments on this page | RSS feed for all comments